PROGRAMMING GUIDE
www.profireenergy.com
1-855-PRO-FIRE
PF2100 MODBUS REGISTER MAP | PROFIRE ENERGY INC.
READ-ONLY INPUT/HOLDING REGISTERS
The Input Registers (300xx) are 2-byte read-only values. They are mirrored in corresponding Holding Registers (400xx) for convenience and to
maintain compatibility with some PLCs.
Use the “Read Input Registers” Command (0x04) to read the Input Registers (300xx).
Use the “Read Holding Registers” Command (0x03) to read the Holding Registers (400xx).
Example 1: Read Single
Reading 1 register starting from Register Offset 3 will result in two data bytes being returned.
The first byte will be the most significant byte of Register Offset 3, and the second byte will
be the least significant byte.
Example 2: Read Multiple
Reading 2 registers starting from Register Offset 3 will result in two data bytes being returned. The first byte will be the most significant byte
of Register Offset 3 and the second byte will be the least significant byte. The next two bytes will contain the value of Register Offset 4.
REGISTER
ADDRESS
(OFFSET) BIT # NAME VALUES DESCRIPTION VER.
30001/40001
(0) BIT 0
BIT 1
BIT 2
BIT 3
Run and Valve Status Bits
RUN
Pilot
Low Fire
High Fire
0 = Not Running
0 = Deenergized
0 = Deenergized
0 = Deenergized
See the following Register Addresses:
10001
10002
10003
10004
2.0+
30002/40002
(1)
BIT 0
BIT 1
BIT 2
BIT 3
BIT 4
BIT 5
BIT 6
BIT 7
BIT 8
BIT 9
BIT 10
BIT 11
BIT 12
BIT 13
Input Status and Flags (Non Latching
Shutdowns)
Level Input
Main Solenoid Feedback
Pilot Solenoid Feedback
High Pressure Input
Proof of Closure
ESD Input
Start Input
Low Pressure
Flame Detected
Flame Test Fail
Unit Failure
Low or High Voltage
HiTemp Alarm
4-20 Card Alarm
0 = Closed
0 = Deenergized
0 = Deenergized
0 = Closed
0 = Closed
0 = Closed
0 = Closed
0 = Closed
0 = No Flame
0 = Flame Test OK
0 = Unit OK
0 = Voltage OK
0 = No Alarm
0 = No Alarm
See the following Register Addresses:
10017
10018
10019
10020
10021
10022
10023
10024
10025
10026
10027
10028
10029
10030
2.0+
30003/40003
(2)
High Temp Thermocouple Reading -50 to 1350°C * This is the current reading of the High Temp Thermo-
couple encoded as a 16-bit signed integer in °C.
2.0+
30004/40004
(3)
Process Thermocouple Reading -50 to 1350°C * This is the current reading of the Process Thermocou-
ple encoded as a 16-bit signed integer in °C.
2.0+
30005/40005
(4)
Aux Thermocouple Reading -50 to 1350°C * This is the current reading of the Aux Thermocouple
encoded as a 16-bit signed integer in °C.
2.0+
30006/40006
(5)
Pilot Flame Quality 0% = No Flame
100% = Good Flame
This number represents the quality of the pilot flame.
The higher the number the better the flame.
2.0+
* These thermocouple readings are all encoded using 16-bit signed integers and are always reported in °C even if the PF2100 is set to display temperature in Fahrenheit.
Data Byte 0
REG OFF 3 MSB
Data Byte 1
REG OFF 3 LSB
Data Byte 0
REG OFF 3 MSB
Data Byte 1
REG OFF 3 LSB
Data Byte 2
REG OFF 4 MSB
Data Byte 3
REG OFF 4 LSB